K-12 RELAY BLOCK

  • K-12 RELAY BLOCK

APPLICATION AREA

The K-12 block of relays is designed for installation in contactor switches or in switching stations of normal design manufactured by SAKOP.
The K-12 block combines the following functions of switching relays:
- leakage shutoff and interlocking relay for 42V or 24 V networks (KZ2 module)
- time-delay relay (KT module)

DESIGN

The K-12 block of relays is encapsulated in an enclosure with the IP-20 index of protection and suitable for mounting on the TS-35 DIN rail. The enclosure is provided with plugged connectors to communicate with the following circuits:
· KZ2 module:
- measuring inputs (interlocking circuit): terminals 9-10,
- measuring inputs (shutoff circuit): terminals 9, 6-7-8,
- functional contacts: terminals 1-2-3 (relay type) and 4-5 (NO)
· KT module:
- control inputs: terminals 11-12,
- functional contacts: terminals 13-14 (NO) and 15-16 (NC)
· power supply 24 V AC: terminals 6-7

INSTALLATION

The enclosure of the relay block is snap-on mounted on a standard top hat mounting rail of 35 mm size.
The module is to be connected to the monitored network according to the application diagram with use of LY-1.5...2.5 mm2 conductors (lug terminals must be squeezed beforehand on bare ends of connecting conductors).

TECHNICAL PARAMETERS


· Rated power supply voltage 24 V AC
· KZ1 module
- interlock input resistance 7 kOhm ± 20%
- shutoff input resistance 4 kOhm ± 20%
· KT module
- delay time 5 – 7 s
· Rated voltage across contacts 250 V AC
· Rated continuous current of contacts 6 A
· Rated insulation voltage 250 V AC
· Dimensions (W x H x D) 45 x 75 x 125 mm
· Index of protection IP 20