ZTSN-... TRANSFORMER UNITS OF NORMAL DESIGN

  • ZTSN-... TRANSFORMER UNITS OF NORMAL DESIGN

APPLICATION AREA

ZTSN-... transformer units of normal design are suitable for local protection and for supplying lighting circuits and other loads with voltages of 133V, 230V or 400V. These devices are designed for operation with connection to three-phase electric power networks with insulated neutral point of the supply transformer, with the rated voltage of 500 V and furnished with central protection against leakages.

APPLICATION CONDITIONS


The device is suitable for working areas of underground operations without the hazard of methane explosion and the ones with the ‘a’ degree of methane explosion hazard as well as with the ‘A’ class of coal dust explosion hazard.

CONFORMITY WITH STANDARDS

ZTSN-... transformer units of normal design are manufactured in line with rules of good engineering practice in the field of occupational safety as well as current state-of-art in technical expertise with consideration to applicable technical standards and the 2014/35/UE Low Voltage Directive.

TECHNICAL PARAMETERS

Power supply voltage:

3x500VAC

Output voltage:

3x133VAC  or

3x230VAC or

3x400VAC

Number of outlets: 1 – 10
Type of electric network:  IT
Index of protection: IP54
Resistance threshold for tripping of
the central leakage protection

15kohm +- 20% @ 400V

7kohm +- 20% @ 230V

7kohm +- 20% @ 133V

Resistance threshold for tripping and reclosure of
the interlocking leakage protection

Rtrip: 25kohm +- 20% @ 400V

Rtrip: 15kohm +- 20% @ 230V

Rtrip: 15kohm +- 20% @ 133V

Rtrip: <1,5Rtrip

Monitoring of the safety (earthing) circuit
continuity for the output (secondary side) network

Rtrip: 80ohm +- 20% 

Rtrip: 60ohm +- 20%