SAKOP 8/... KITS

  • SAKOP 8/... KITS

The product is approved for application both on surface and in underground workings of mining operations

APPLICATION AREA

  •  For repairs and making connections on electric power cables with rated voltage up to 3.6/6 kV
    - in insulation of soft PVC, polyethylene, cross-linked PE and in coatings and sheaths of thermoplastic materials (shielded, non-shielded).
    - wrapped in paper insulation and secured with lead coating or armour
  • For repairs and making connections on cabtyre cables with rated voltage up to 3.6/6 kV
  • Enables connections between cables/conductors with different cross-sections of working cores up to 240 mm2
  • Suitable for direct burying into ground

TECHNICAL PARAMETERS

  •   Insulation of individual cores is restored:
    - with PVC tape or with self-bonding adhesive tape (for cables with thermoplastic insulation and for cabtyre cables
    - oil-soaked tape for electric insulation (TPK oilcloth) or self-bonding insulating tape (for cables wrapped in paper insulation)
  •  Metallic shields of individual cores are mutually connected with tape made of copper mesh
  • Overall cable shield is connected with a copper cord
  • Outer sheath of the joint box is made of polycarbonate (resistant to flame propagation) and then filled with two-component polyurethane compound
  • Each kit comprises all components and instruction manuals for making the joint
  • The joint box can be connected to live voltage right after installation

SPECIFICATION

  SAKOP
8/T1 E
SAKOP
8/T2 E
SAKOP
8/1 (P)
SAKOP
8/2 (P)
SAKOP
8/3 (P)
L [mm] 200 350 300,350,450,550 400,450,550,650 600,850,1100,1350
D [mm] 45 47 80 100 130
D1 [mm] 14 14 27 35 57
D2 [mm] 35 40 60 72 80