SAKOP 2/5-3B TERMINAL CABINET OF NORMAL DESIGN

  • SAKOP 2/5-3B TERMINAL CABINET OF NORMAL DESIGN

APPLICATION AREA

SAKOP-2/5-3B (-N, -X, -NX) branching terminal cabinet of normal design is suitable for the following purposes:

  •  Making straight through connections between two sections of electric power cables
  •  Making a straight through connection between two sections of cables with an additional secured branching from the power supply mains line to connect any desired equipment

APPLICATION CONDITIONS

The device is suitable for working areas of underground operations without the hazard of methane explosion and the ones with the ‘a’ degree of methane explosion hazard as well as with the ‘A’ class of coal dust explosion hazard.

CONFORMITY WITH STANDARDS

SAKOP 2/5-3B (-N, -X, -NX) branching terminal cabinet of normal design are manufactured in line with rules of good engineering practice in the field of occupational safety as well as current state-of-art in technical expertise with consideration to applicable technical standards and the 2014/35/UE Low Voltage Directive.

DESIGN

Standard terminal cabinet are made of carbon steel sheets protected against corrosion by coating with paint of the RAL 7032 colour. Terminal cabinets made of stainless steel are also available upon request (designated with the ‘N’ letter in their product code).

TECHNICAL PARAMETERS

Cabinet type
SAKOP 2/5-3B (-N)
SAKOP 2/5-3BX (-N)
Rated voltage
500 V
500 V
Rated current of terminals for straight
through connections
320 A – branched
current
320 A – branched
current
Maximum cross-section of the incoming
cable (inlet chamber)
120 mm2
120 mm2
Maximum cross-section of the outgoing
cable (branching chamber)
70 mm2
70 mm2
Maximum permissible current in the
branching line
160 A
160 A
Cable inlet bushings of WK type for
cables with the following diameters:
- WK4: 40 – 50 mm
- WK5: 50 – 60 mm
3
0
Enclosure index of protection
IP 54
IP 54
Overall dimensions (W x H x D)
150 x 150 x 100 mm
150 x 150 x 100 mm