SAKOP 1/... KITS for repairs and making joints on electric power cables and cabtyre conductors for rated voltage up to 6 kV

  • SAKOP 1/... KITS for repairs and making joints on electric power cables and cabtyre conductors for rated voltage up to 6 kV

The product is approved for application both on surface and in underground workings of mining operations

APPLICATION AREA

  •  For repairs and making connections on electric power cables with rated voltage up to 3.6/6 kV
    - protected by insulation, coating and sheaths made of thermoplastic materials (both shielded and unshielded)
    - wrapped in paper insulation and secured with lead coating or armour
  • For repairs and making connections on cabtyre cables with rated voltage up to 3.6/6 kV
  • Enables connections between cables/conductors with different cross-sections of working cores up to 240 mm2 Suitable for direct burying into ground

TECHNICAL PARAMETERS

  •  Insulation of individual cores is restored:
    - in insulation of soft PVC, polyethylene, cross-linked PE and in coatings and sheaths of thermoplastic materials (shielded, non-shielded).
    - oil-soaked tape for electric insulation (TPK oilcloth) or self-bonding insulating tape (for cables wrapped in paper insulation)
  • Metallic shields of individual cores are mutually connected with tape made of copper mesh
  • Overall cable shield is connected with a copper cord
  • Outer sheath of the joint box is made of flame retardant soft PVC and flame retardant rubber and then filled with two-component polyurethane compound
  • Each kit comprises all components and instruction manuals for making the joint
  • The joint box can be connected to live voltage right after installation

SPECIFICATION

Cables in insulation made
of thermoplastic materials
and cabtyre cables
Crosssection
[mm2]
Outer sheath
L [mm], D[mm]
Cables in paper
insulation
Crosssection
[mm2]
Outer sheath
L [mm], D[mm]
SAKOP 1/0 up to 50 L=350, D=63 SAKOP 1/1P up to 70 L= 500, D= 80
SAKOP 1/1 up to 70 L=380, D=80 SAKOP 1/2P up to 120 L= 600, D= 90
SAKOP 1/2 up to 120 L=420, D=90 SAKOP 1/3P up to 150 L= 800, D= 125
SAKOP 1/3 up to 150 L=600, D=125 SAKOP 1/3aP up to 240 L= 1000, D= 125
SAKOP 1/3a up to 240 L=800, D=125 SAKOP 1/3bP up to 240 L= 1200, D= 125
SAKOP 1/3b up to 240 L=1000, D=125      
SAKOP 1/3c up to 240 L=1200, D=125      