INTERFACING JOINT BOX SAKOP M-6/PYT FOR VOLTAGES UP TO 3.6/6 kV

  • INTERFACING JOINT BOX SAKOP M-6/PYT FOR VOLTAGES UP TO 3.6/6 kV

APPLICATION AREA

  •  The kit for connection of three core electric power cables designed for rated voltage of 3.6/6 kV protected by soft PVC insulation of the Y(A)KY(Fty)… type with three core electric power cables wrapped in paper insulation soaked with nondripping substance and coated in lead armour H(A)KnyFtA(y)…
  •  Enables connection of cables with different cross-section of working cores ranging from 16 to 240 mm2
  •  Suitable for direct burying into ground

TECHNICAL PARAMETERS

  •  Working cores can be connected together by means of crimped terminals or terminals with secure lock bolts (supplied upon request)
  •  Cable insulation is restored by means of self-bonding adhesive tape for high voltages
  •  Restoration of the return line by means of PLC woven copper tape
  •  Outer encapsulation is made of a heat shrink tube stud or coiled crust
  •  Each kit comprises all components and instruction manuals for making the joint
  •  The joint box can be connected to live voltage right after installation

SPECIFICATION

Type
Cross-section [mm2]
Outer sheath
 
SAKOP M-6/PYT-1
16 – 70
heat shrink stud tube
SAKOP M-6/PYT-2
95 – 120
heat shrink stud tube
SAKOP M-6/PYT-3
150 – 240
heat shrink stud tube
SAKOP M-6/PYT-4
16 – 70
heat shrink crust
SAKOP M-6/PYT-5
95 – 120
heat shrink crust
SAKOP M-6/PYT-6
150 – 240
heat shrink crust